JA-80S

1 Installation

alarmsysteemexpert
Installation should only be done by a certified technician approved by an authorized distributor.
The detector is usually mounted on the ceiling, at least 60cm away from a wall. It can protect a room up to 50m³. Install a minimum of 2 smoke detectors in a corridor longer than 9 meters, one on each side.

Avoid installation in areas where:
- There is no natural air circulation (wall recesses, corners, ridge of
a roof)
- Areas with dust, cigarette smoke or steam.
- Rapid air changes such as fans, air conditioning output, or high-rise heaters.
Avoid placement above stoves in kitchens where steam, smoke, and oil vapor can reduce the operation of the smoke detector. Avoid placement near metal objects that may block the radio signal.

Warning: Most false alarms come from poor positioning of the smoke detector.

Installation:
1. Open the detector (twist the back cover)
2. Mount the back in the desired location.
3. Do not install the battery yet and leave the housing open. Follow the teach-in instructions of the central unit or universal receiver.
4. Basics of teach-in are
1. Enter teach-in mode in the central unit by pressing "1" on the control panel in service mode.
2. Insert the battery into the detector. The detector will teach itself to the central unit and will do a self-test. (20 sec) This should be done in a smoke-free room with clean air with a temperature of about +20°C.
3. Exit teach-in mode by pressing "#".
To teach-in the detector after the battery has been installed, first remove the battery and press the test button to clear the detector of residual charge and prepare the detector for teach-in.
4. After closing the detector, check that the 2 halves of the housing are firmly attached to each other.
After installing the battery, the detector will take one minute to stabilize, during stabilization the detector's light will be on continuously.

2 Jumpers

SIREN ON/OFF (Siren on/off) Allows you to disable the internal siren (OFF = disabled)
FIRE/INST (fire/direct) Selects what is the natural response of the detector in the central station.

Jumper

at position FIRE: The central station responds as a fire alarm regardless of whether the system is on or off.

Jumper

at position INST: The central station responds with a fire alarm only when the system is on. This setting is useful if the user wishes, for example, to allow smoking in a room or the fireplace is on or while the system is off and therefore authorized persons are present.
WARNING: In the INST position of the sweater, if the system is off, the detector will not respond to smoke. The FIRE/INST sweater only has an effect if in the Oasis control center is set to neutral response to the detector's address. The sweater also has no effect in combination with UC-8x or AC-8x receivers. If the detector housing is opened, a tamper message is sent.
alarmsysteemexpert

3 Testing the detector

The operation of the detector can be tested by holding down the test button for, say, 1 second. This activates the siren and the LED will flash. The signal strength and quality can be measured by the control center in the service mode. While testing with the test button, the detector will send signals that cannot cause a fire alarm in the control center.

Warning: Do not start a fire in a building to test the detector. Instead, use smoke-simulating spray to perform a test.

4 Turning off siren during an alarm

During a fire alarm, the LED will flash and the internal siren will sound. Pressing the test button will turn off the siren, but the LED will continue to flash until the smoke is gone.

5 Alarm memory in the detector

Normally the detector will alarm until the smoke is gone and the alarm will be stored in the central unit's memory. If desired, the internal memory can be activated by pressing and holding the test button when inserting the battery. In this mode, the detector will continue to alarm until the test button is pressed.

6 Fault Indication

The detector will periodically perform a self-test. If an error is registered, the LED will flash rapidly. Remove the battery and replace it after 20 seconds. If after one minute the LED starts flashing again, send the detector for repair.

The detector monitors the battery voltage. If it gets too low, the detector will send a signal to the alarm center to alert the user or technician. The detector will continue to operate and the LED will flash every minute. Battery replacement should not be delayed longer than 2 weeks. Replacement should be done by a certified installer when the central unit is in Service mode.
Do not simply throw away empty batteries, follow local rules for disposing of batteries.

8 Removing the detector from the system

If the detector is removed from the system, the control panel will report this. The detector must also be removed from the central unit before the detector itself is removed.

Login

Forgot your password?

Don't have an account yet?
Create a free account and enjoy many benefits.